Flanged Inverted Barrel Steam Trap

881F Inverted Bucket Steam TrapWhen
steam enters the inverted bucket, the upside-down bucket generates
upward buoyancy, and the inverted bucket is connected to the lever to
drive the valve core to close the valve. There is a small hole on the
inverted bucket, which can automatically exhaust the air, when part of
the steam is discharged from the small hole, the other part of the steam
produces condensate, the inverted bucket loses buoyancy and sinks, and
the inverted bucket is connected to the lever to drive the valve core to
open the valve. When the steam enters the inverted bucket again, the
valve closes again, circulates and drains intermittently.
Inverted
(placed) bucket steam trap It is the use of condensate and steam
density difference working principle, the internal structure is
connected by the lever system to the inverted bucket, overcome the steam
pressure switch inverted bucket trap inside is an inverted bucket for
the level sensitive parts, the opening of the inverted bucket down. When
the unit is first started, air and low-temperature condensate appear in
the pipe, and the trap is fully open, the air and low-temperature
condensate are quickly discharged, and the device quickly increases the
temperature. When the steam enters the inverted barrel, the inverted
barrel generates upward buoyancy, and the inverted barrel is connected
to the lever to drive the valve core to close the valve. There is a
small hole on the inverted bucket, which can automatically exhaust air,
when a part of the steam is discharged from the small hole, the other
part of the steam produces condensate, the inverted bucket loses
buoyancy and sinks, and the inverted bucket is connected to the lever to
drive the valve core to open the valve. When the steam enters the
inverted bucket again, the valve closes again, circulates and drains
intermittently.